York Furnace 5 Red Flashes (YP9C Modulating)
Safety faultShown as: Five red flashes, two-second pause, repeating
The rollout switch or the condensate pressure switch is open. A rollout trip means flame or hot gas escaped the burner compartment; a condensate switch trip means the drain has backed up.
Manual wording: “Five Red Flashes - Rollout switch or condensate pressure switch open. Check the rollout switch(es) on the burner assembly. It is a manual reset switch... If it cannot be reset or if the switch trips again, contact a qualified serviceman.”
Documented for: YP9C, YPLC modulating furnaces
Likely causes, most common first
- Flame rollout switch tripped on the burner assembly
- Condensate pressure switch open from a backed-up drain
What you can safely check yourself
- Check the condensate drain line and trap for a clog and clear standing water from the drain pan area
- Check the outside vent and intake pipes for blockage
- If you smell exhaust fumes or a CO alarm sounds, leave the house and call for service from outside
When to call a technician
The manual is explicit: if the rollout switch cannot be reset or trips again, contact a qualified serviceman. A repeat rollout can mean a cracked heat exchanger and a carbon monoxide risk - do not keep resetting it.
A York furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation Manual - Modulating ECM Residential Gas Furnace with ECM Motor, Models YP9C*C / TP9C*C / CP9C*C / LP9C*C (Up to 98% Modulating Multi-position), 1083292-UIM-A-0114 (Johnson Controls Unitary Products (York), YP9C*C (York Affinity modulating), and the identical TP9C / CP9C / LP9C chassis) · checked 2026-08-25