HVAC Code Lookup

Mitsubishi Electric fault codes

53 documented codes for Mitsubishi Electric mini-splits, each cited to the manufacturer's own manual. Find your code in the table, then jump to what it means, the likely causes, what you can safely check, and when to call a technician.

Mitsubishi Electric ductless systems use two different fault-code displays. Residential M-Series wall units (MSZ/MSY indoor with MUZ/MUY single-zone or MXZ multi-zone outdoor) that ship with only an infrared handheld remote report faults by blinking the OPERATION INDICATOR lamp on the indoor unit a set number of times - this is the 'blinking N times' pattern homeowners search for. The same A-Control platform, when a wired remote controller (PAR-series or MHK-series thermostat) is connected, displays the alphanumeric check codes (P1-PL, E0-EF, F3/F5, U1-UP) plus their 4-digit equivalents. P-Series / Mr. Slim equipment (PUZ outdoor, PKA/PLA/PEAD indoor) uses the same alphanumeric check-code set, so the code meanings below apply across M-Series and P-Series. Codes beginning with P and E are detected by the indoor unit; codes beginning with U and F are detected by the outdoor unit.

Looking it up by flash count?

If you counted LED flashes rather than reading a code number, these are the codes that start with that many flashes:

  • 1 flashes: 1 blink (Miswiring or serial signal error)
  • 2 flashes: 2 blinks (Indoor coil thermistor or room temperature thermistor error)
  • 3 flashes: 3 blinks (Indoor fan motor error)
  • 4 flashes: 4 blinks (Indoor control system error)
  • 5 flashes: 5 blinks (Outdoor power system error)
  • 6 flashes: 6 blinks (Outdoor thermistor error)
  • 7 flashes: 7 blinks (Outdoor control system error)
  • 14 flashes: 14 blinks or more (Other abnormality)

Mini-Split codes

CodeMeaningSeverity
1 blinkUpper OPERATION INDICATOR lamp blinks steadily: 0.5 second ON, 0.5 second OFF, continuouslyMiswiring or serial signal errorSoft lockout
2 blinksUpper OPERATION INDICATOR lamp blinks 2 times, then 2.5 seconds off, repeatingIndoor coil thermistor or room temperature thermistor errorSoft lockout
3 blinksUpper OPERATION INDICATOR lamp blinks 3 times, then 2.5 seconds off, repeatingIndoor fan motor errorSoft lockout
4 blinksUpper OPERATION INDICATOR lamp blinks 4 times, then 2.5 seconds off, repeatingIndoor control system errorHard lockout
5 blinksUpper OPERATION INDICATOR lamp blinks 5 times, then 2.5 seconds off, repeatingOutdoor power system errorSoft lockout
6 blinksUpper OPERATION INDICATOR lamp blinks 6 times, then 2.5 seconds off, repeatingOutdoor thermistor errorSoft lockout
7 blinksUpper OPERATION INDICATOR lamp blinks 7 times, then 2.5 seconds off, repeatingOutdoor control system errorHard lockout
14 blinks or moreUpper OPERATION INDICATOR lamp blinks 14 or more times, then 2.5 seconds off, repeatingOther abnormalitySoft lockout
lamp lit steady, outdoor unit will not runUpper OPERATION INDICATOR lamp lights up solid (not blinking) while the outdoor unit does not operateOutdoor control system errorHard lockout
Mode ConflictUpper OPERATION INDICATOR lamp lights and lower lamp blinks, then 2.5 seconds off, repeatingOperation mode conflict on a multi-zone MXZ system, not a hardware failureStatus
P1Room temperature thermistorSoft lockout
P2Pipe temperature thermistor / liquidSoft lockout
P4Drain sensor error / drain float switch connector openSoft lockout
P5Drain overflow protection / drain pump errorSoft lockout
P6Freezing or overheating protection is workingWarning
P8Pipe temperature errorSoft lockout
P9Pipe temperature thermistor / condenser-evaporatorSoft lockout
PAForced compressor stop due to a water leakage abnormalityHard lockout
PLAbnormal refrigerant circuitHard lockout
E0Remote controller transmission errorSoft lockout
E1Remote controller control board errorHard lockout
E2Remote controller control board error - clock functionHard lockout
E3Remote controller transmission errorSoft lockout
E4Remote controller signal receiving error detected by the indoor unitSoft lockout
E5Remote controller transmitting error detected by the indoor unitSoft lockout
E6Indoor/outdoor unit communication errorSoft lockout
E7Indoor/outdoor unit communication errorSoft lockout
E8Indoor/outdoor unit communication error - signal receiving error detected by the outdoor unitSoft lockout
E9Indoor/outdoor unit communication error - transmitting error detected by the outdoor unitSoft lockout
EAMiswiring of the indoor/outdoor unit connecting wire, or too many indoor unitsSoft lockout
EbMiswiring of the indoor/outdoor unit connecting wire - converseSoft lockout
ECStartup time overSoft lockout
EdSerial communication error inside the outdoor unitSoft lockout
EECombination error between the indoor and outdoor unitsHard lockout
EFNon-defined check codeWarning
FbIndoor unit control system errorHard lockout
F3The 63L low pressure switch connectorSoft lockout
F5The 63H high pressure switch connectorSoft lockout
U1Abnormal high pressureSoft lockout
U2Abnormal high discharge temperature or high compressor surface temperature, which usually means the system is short of refrigerantSoft lockout
U3Open or short circuit of the outdoor discharge temperature thermistorSoft lockout
U4Open or short circuit of one of the outdoor unit thermistorsSoft lockout
U5Abnormal temperature of the heatsinkSoft lockout
U6Power module abnormality / compressor overcurrent interruptionSoft lockout
U7Too low superheat due to low discharge temperatureSoft lockout
U8Outdoor fan motor protection stopSoft lockout
U9Power supply abnormality - overvoltage, undervoltage, overcurrent or a bad power synchronous signalSoft lockout
UdOverheat protectionSoft lockout
UEAbnormal pressure at the 63HS high pressure sensorSoft lockout
UFCompressor overcurrent interruption with the compressor lockedSoft lockout
UHCurrent sensor errorSoft lockout
ULAbnormal low pressureSoft lockout
UPCompressor overcurrent interruptionSoft lockout

Mitsubishi Electric mini-split Lamp Lit Steady, Outdoor Unit Will Not Run: Outdoor control system error

Hard lockoutShown as: Upper OPERATION INDICATOR lamp lights up solid (not blinking) while the outdoor unit does not operate

Outdoor control system error. The inverter or outdoor control board cannot read its nonvolatile memory, and the outdoor unit does not operate. The indoor lamp stays lit rather than blinking.

Manual wording: “Outdoor control system - Upper lamp lights up. Outdoor unit does not operate.”

Documented for: MSZ-GL and MSY-GL indoor units

Likely causes, most common first

  1. Defective inverter P.C. board
  2. Defective outdoor electronic control P.C. board

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The manual's remedy is to read the LED blink pattern on the outdoor boards and replace the failed board. Call a technician.

Source

Mitsubishi Electric mini-split Mode Conflict: Operation mode conflict on a multi-zone MXZ system, not a hardware failure

StatusShown as: Upper OPERATION INDICATOR lamp lights and lower lamp blinks, then 2.5 seconds off, repeating

Operation mode conflict on a multi-zone MXZ system, not a hardware failure. Two indoor units were set to opposite modes (one to COOL or DRY, one to HEAT). A single MXZ outdoor unit can only do one at a time, so whichever indoor unit started first wins and the other one stops.

Manual wording: “The operation mode of the each indoor unit is differently set to COOL (includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at first has the priority.”

Documented for: MSZ-GL and MSY-GL indoor units on MXZ-2C, MXZ-3C, MXZ-4C and MXZ-5C multi-zone outdoor units

Likely causes, most common first

  1. One indoor unit set to COOL or DRY while another on the same outdoor unit is set to HEAT

What you can safely check yourself

  • Set every indoor unit on the system to the same mode (all cooling, or all heating)
  • Check the mode setting on each remote, including any room you are not using
  • Note that DRY counts as cooling for this purpose

When to call a technician

If every head is already set to the same mode and one still refuses to run, have a technician check the system.

Sources

Mitsubishi Electric mini-split code P1: Room temperature thermistor

Soft lockout

Room temperature thermistor (TH1) error. The intake air temperature sensor reads short circuit (194F or more) or open circuit (-40F or less), so the unit cannot measure room temperature.

Manual wording: “Room temperature thermistor (TH1) ... Short: 90C [194F] or more, Open: -40C [-40F] or less”

Documented for: A-Control indoor units (PKA-A, PLA-A, PEAD-A and M-Series with a wired controller)

Likely causes, most common first

  1. Defective thermistor characteristics
  2. Contact failure of connector CN20 on the indoor controller board (insert failure)
  3. Breaking of wire or contact failure of thermistor wiring
  4. Defective indoor controller board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once to see if it resets

When to call a technician

Checking the thermistor resistance and its connector means opening the indoor unit and working at the control board. Call a technician.

Sources

Mitsubishi Electric mini-split code P2: Pipe temperature thermistor / liquid

Soft lockout

Pipe temperature thermistor / liquid (TH2) error. The indoor liquid-line sensor reads short circuit (194F or more) or open circuit (-40F or less).

Manual wording: “Pipe temperature thermistor/Liquid (TH2) ... Short: 90C [194F] or more, Open: -40C [-40F] or less”

Documented for: A-Control indoor units (PKA-A, PLA-A, PEAD-A and M-Series with a wired controller)

Likely causes, most common first

  1. Defective thermistor characteristics
  2. Contact failure of connector CN44 on the indoor controller board (insert failure)
  3. Breaking of wire or contact failure of thermistor wiring
  4. Defective refrigerant circuit driving the thermistor to 194F or more or -40F or less
  5. Defective indoor controller board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once to see if it resets

When to call a technician

If the pipe temperature really is that far out of range the refrigerant circuit is at fault, which is a technician job either way.

Sources

Mitsubishi Electric mini-split code P4: Drain sensor error / drain float switch connector open

Soft lockout

Drain sensor error / drain float switch connector open. The float switch connector CN4F on the indoor controller board is open, so the unit cannot confirm the condensate level is safe.

Manual wording: “Contact failure of drain float switch (CN4F) - Extract when the connector of drain float switch is disconnected.”

Documented for: A-Control indoor units with a drain float switch (PKA-A, PLA-A, PEAD-A, PCA-A)

Likely causes, most common first

  1. Contact failure of the float switch connector (insert failure)
  2. Float switch connector disconnected
  3. Defective indoor controller board

What you can safely check yourself

  • Check the condensate drain line outside for a clog, kink or blockage
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The float switch connector is inside the indoor unit on the control board. Never short or bypass the float switch to clear this code - it is the protection that keeps condensate from overflowing into the room.

Source

Mitsubishi Electric mini-split code P5: Drain overflow protection / drain pump error

Soft lockout

Drain overflow protection / drain pump error. The float switch stayed underwater for 1 minute 30 seconds with the drain pump running, so the compressor and indoor fan shut off to stop water overflowing.

Manual wording: “Drain overflow protection operation - Suspensive abnormality, if drain float switch is detected to be underwater for 1 minute and 30 seconds continuously with drain pump on.”

Documented for: A-Control indoor units with a condensate pump (PKA-A, PLA-A, PEAD-A, PCA-A)

Likely causes, most common first

  1. Malfunction of the drain pump
  2. Defective drainage - clogged drain pump or clogged drain pipe
  3. Defective drain float switch, or the float caught on a moving part
  4. Defective indoor controller board

What you can safely check yourself

  • Check the condensate drain line outside for a clog, kink, ice or debris
  • Check the air filters and clean them, since a dirty filter can make condensate ripple onto the float switch
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Clearing the internal drain pan, drain pump or float switch means opening the indoor unit. Call a technician, and do not run the unit while it is spilling water.

Source

Mitsubishi Electric mini-split code P6: Freezing or overheating protection is working

Warning

Freezing or overheating protection is working. In cooling the indoor coil dropped below 5F for 3 minutes twice inside 16 minutes; in heating the coil went above 158F twice inside 30 minutes. Either way the unit stops itself to protect the coil.

Manual wording: “Freezing/overheating protection is working ... 1 Clogged filter (reduced airflow) 2 Short cycle of air path”

Documented for: A-Control indoor units (PKA-A, PLA-A, PEAD-A and M-Series with a wired controller)

Likely causes, most common first

  1. Clogged filter reducing airflow
  2. Short cycle of the air path - supply air blowing straight back into the return
  3. Low-load (cooling) or overload (heating) operation outside the tolerance range
  4. Defective indoor fan motor
  5. Defective outdoor fan control
  6. Overcharge of refrigerant
  7. Defective (clogged) refrigerant circuit

What you can safely check yourself

  • Remove and clean or replace the air filters - the manual's first listed check is 'Check clogs of the filter'
  • Remove anything blocking the indoor unit air inlet or outlet, including furniture, curtains and boxes
  • Check that the outdoor unit is clear of snow, ice, leaves and debris
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

If the filters are clean and airflow is unobstructed and P6 comes back, the fan motor or the refrigerant charge is the problem and a technician has to diagnose it.

Sources

Mitsubishi Electric mini-split code P8: Pipe temperature error

Soft lockout

Pipe temperature error. The indoor coil never reached the expected cooling or heating temperature range within the allowed time after the compressor started, which means the coil is not actually cooling or heating the way it should.

Manual wording: “Pipe temperature - Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start”

Documented for: A-Control indoor units (PKA-A, PLA-A, PEAD-A and M-Series with a wired controller)

Likely causes, most common first

  1. Only a slight temperature difference between room air and pipe temperature - shortage of refrigerant, thermistor holder fallen off the pipe, or a defective refrigerant circuit
  2. Reverse connection of the extension pipe (on multi-unit installations)
  3. Reverse wiring of the indoor/outdoor connecting wire (on multi-unit installations)
  4. Defective detection by the room and pipe temperature thermistors
  5. Stop valve is not opened completely

What you can safely check yourself

  • Check that the outdoor unit is clear of snow, ice and debris
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Every cause on the manual's list - refrigerant charge, pipe routing, stop valves, sensor mounting - is a technician job.

Sources

Mitsubishi Electric mini-split code P9: Pipe temperature thermistor / condenser-evaporator

Soft lockout

Pipe temperature thermistor / condenser-evaporator (TH5) error. The indoor gas-line sensor reads short circuit (194F or more) or open circuit (-40F or less).

Manual wording: “Pipe temperature thermistor/Condenser-Evaporator (TH5) ... Short: 90C [194F] or more, Open: -40C [-40F] or less”

Documented for: A-Control indoor units (PKA-A, PLA-A, PEAD-A and M-Series with a wired controller)

Likely causes, most common first

  1. Defective thermistor characteristics
  2. Contact failure of connector CN44 on the indoor controller board (insert failure)
  3. Breaking of wire or contact failure of thermistor wiring
  4. Thermistor driven past 194F or below -40F by a defective refrigerant circuit
  5. Defective indoor controller board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once to see if it resets

When to call a technician

Thermistor testing happens at the indoor control board. Call a technician.

Sources

Mitsubishi Electric mini-split code PA: Forced compressor stop due to a water leakage abnormality

Hard lockout

Forced compressor stop due to a water leakage abnormality. The unit saw the coil running far colder than room air for a total of 30 minutes AND the drain float switch underwater for more than 15 minutes, so it shut the compressor down. This state will not clear until main power is reset.

Manual wording: “Forced compressor stop (due to water leakage abnormality) ... Once the water leakage abnormality is detected, abnormality state will not be released until the main power is reset.”

Documented for: A-Control indoor units with a drain float switch and water-leakage detection

Likely causes, most common first

  1. Drain pump trouble
  2. Defective drainage - drain pump clogging or drain pipe clogging
  3. Open circuit of the float switch
  4. Contact failure of the float switch connector
  5. Dew condensation on the float switch, or drain water rippling because of a clogged filter
  6. Extension piping or connecting-wire mismatch on twin/triple/quadruple systems

What you can safely check yourself

  • Check the condensate drain line outside for a clog, kink, ice or debris
  • Remove and clean or replace the air filters - the manual lists filter clogging as a cause of the float switch tripping
  • Turn the system off at the breaker, wait one minute, and turn it back on once, since the manual says the abnormality is only released by resetting main power

When to call a technician

If PA returns after a power reset, the drain pump, float switch or piping is at fault. Call a technician before running it again - the unit stopped itself specifically to avoid a water leak.

Sources

Mitsubishi Electric mini-split code PL: Abnormal refrigerant circuit

Hard lockout

Abnormal refrigerant circuit. During cooling, dry or auto-cooling, the compressor ran 30 seconds or more while the liquid pipe or condenser/evaporator temperature hit 167F or higher. The error is latched and will not clear until power is reset.

Manual wording: “Abnormal refrigerant circuit ... These detected errors will not be cancelled until the power source is reset.”

Documented for: A-Control indoor and outdoor units

Likely causes, most common first

  1. Abnormal operation of the 4-way (reversing) valve
  2. Disconnection of or leakage in refrigerant pipes
  3. Air in the refrigerant piping
  4. Indoor fan not rotating - defective fan motor or defective indoor control board
  5. Defective (clogged) refrigerant circuit

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once, since the manual says the error stays latched until the power source is reset

When to call a technician

The manual says that when this error occurs the 4-way valve must be replaced, and the refrigerant circuit recovered, vacuumed and dried. This is entirely a technician job.

Sources

Mitsubishi Electric mini-split code E0: Remote controller transmission error

Soft lockout

Remote controller transmission error. The wired remote controller could not receive any transmission from the indoor unit for 3 minutes (or a sub controller received nothing for 2 minutes).

Manual wording: “Remote controller transmission error(E0)/signal receiving error(E4) - Abnormal if main or sub remote controller cannot receive any transmission normally from indoor unit of refrigerant address 0 for 3 minutes.”

Documented for: A-Control systems with a wired remote controller

Likely causes, most common first

  1. Contact failure at the transmission wire of the remote controller
  2. All remote controllers are set as 'sub' - in that case E0 shows on the remote and E4 shows on the outdoor board LEDs
  3. Miswiring of the remote controller
  4. Defective transmitting/receiving circuit of the remote controller or indoor controller board
  5. Noise on the remote controller transmission wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Remote controller wiring, main/sub addressing and board swaps are technician tasks.

Sources

Mitsubishi Electric mini-split code E1: Remote controller control board error

Hard lockout

Remote controller control board error. Data cannot be read normally from the nonvolatile memory of the remote controller control board.

Manual wording: “Remote controller control board - Abnormal if data cannot be read normally from the nonvolatile memory of the remote controller control board. (Check code: E1)”

Documented for: A-Control systems with a wired remote controller

Likely causes, most common first

  1. Defective remote controller

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The manual's only remedy is to replace the remote controller. Call a technician.

Sources

Mitsubishi Electric mini-split code E2: Remote controller control board error - clock function

Hard lockout

Remote controller control board error - clock function. The clock function of the remote controller cannot operate normally.

Manual wording: “Abnormal if the clock function of remote controller cannot be operated normally. (Check code: E2)”

Documented for: A-Control systems with a wired remote controller

Likely causes, most common first

  1. Defective remote controller

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The manual's only remedy is to replace the remote controller. Call a technician.

Sources

Mitsubishi Electric mini-split code E3: Remote controller transmission error

Soft lockout

Remote controller transmission error. The remote controller could not find a free slot on the transmission path for 6 seconds and could not transmit, or its sent and received data disagreed 30 times in a row.

Manual wording: “Remote controller transmission error(E3)/signal receiving error(E5) - Abnormal if remote controller could not find blank of transmission path for 6 seconds and could not transmit.”

Documented for: A-Control systems with a wired remote controller

Likely causes, most common first

  1. Two remote controllers are both set as 'main'
  2. One remote controller is connected to 2 or more indoor units
  3. Repetition of refrigerant address
  4. Defective transmitting/receiving circuit of the remote controller or the indoor controller board
  5. Noise has entered the remote controller transmission wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Setting main/sub, checking addresses and diagnosing the controller are technician tasks.

Sources

Mitsubishi Electric mini-split code E4: Remote controller signal receiving error detected by the indoor unit

Soft lockout

Remote controller signal receiving error detected by the indoor unit. The indoor controller board received no data from the remote controller board for 3 minutes (or no signal at all for 2 minutes).

Manual wording: “Abnormal if indoor controller board cannot receive any data normally from remote controller board or from other indoor controller board for 3 minutes. (Check code: E4)”

Documented for: A-Control systems with a wired remote controller

Likely causes, most common first

  1. Contact failure at the remote controller transmission wire
  2. All remote controllers set as 'sub'
  3. Miswiring of the remote controller
  4. Defective transmitting/receiving circuit of the remote controller or indoor controller board
  5. Noise on the remote controller transmission wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Remote controller wiring and main/sub addressing are technician tasks.

Sources

Mitsubishi Electric mini-split code E5: Remote controller transmitting error detected by the indoor unit

Soft lockout

Remote controller transmitting error detected by the indoor unit. The indoor controller board could not find a free slot on the transmission path, or its sent and received data disagreed 30 times in a row.

Manual wording: “Abnormal if indoor controller board could not find blank of transmission path. (Check code: E5)”

Documented for: A-Control systems with a wired remote controller

Likely causes, most common first

  1. Two remote controllers both set as 'main'
  2. One remote controller connected to 2 or more indoor units
  3. Repetition of refrigerant address
  4. Defective transmitting/receiving circuit of the indoor controller board or remote controller
  5. Noise has entered the remote controller transmission wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Diagnosing the remote controller and the indoor board is a technician task.

Sources

Mitsubishi Electric mini-split code E6: Indoor/outdoor unit communication error

Soft lockout

Indoor/outdoor unit communication error (signal receiving error). The indoor controller board received no signal from the outdoor unit for 6 minutes after power-on, or for 3 minutes during operation. The most common cause is a problem with the wire running between the indoor and outdoor units.

Manual wording: “Indoor/outdoor unit communication error (Signal receiving error) - Abnormal if indoor controller board cannot receive any signal normally for 6 minutes after turning the power on.”

Documented for: A-Control indoor and outdoor units (M-Series and P-Series)

Likely causes, most common first

  1. Contact failure, short circuit or miswiring (reverse wiring) of the indoor/outdoor unit connecting wire
  2. Defective transmitting/receiving circuit of the indoor controller board
  3. Defective transmitting/receiving circuit of the outdoor controller board
  4. Noise has entered the indoor/outdoor unit connecting wire

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Check that the outdoor unit is clear of snow, ice and debris and that nothing has damaged the wire cover
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The S1-S2-S3 connecting wire carries line voltage. Checking, tightening or correcting it, and any board replacement, is a technician job.

Sources

Mitsubishi Electric mini-split code E7: Indoor/outdoor unit communication error

Soft lockout

Indoor/outdoor unit communication error (transmitting error). The indoor controller board transmitted a '0' but a '1' was read back 30 times in a row, so the indoor unit cannot reliably send to the outdoor unit.

Manual wording: “Indoor/outdoor unit communication error (Transmitting error) - Abnormal if 1 receiving is detected 30 times continuously though indoor controller board has transmitted 0.”

Documented for: A-Control indoor and outdoor units (M-Series and P-Series)

Likely causes, most common first

  1. Defective transmitting/receiving circuit of the indoor controller board
  2. Noise has entered the power supply
  3. Noise has entered the outdoor control wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The manual's remedy is to power cycle and, if it repeats, replace the indoor controller board. Call a technician.

Sources

Mitsubishi Electric mini-split code E8: Indoor/outdoor unit communication error - signal receiving error detected by the outdoor unit

Soft lockout

Indoor/outdoor unit communication error - signal receiving error detected by the outdoor unit. The outdoor controller board received no signal normally for 6 minutes after power-on, or 3 minutes during operation.

Manual wording: “E8 Indoor/outdoor unit communication error - Signal receiving error (Outdoor unit)”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Indoor/outdoor unit connecting wire has contact failure or is miswired
  2. Defective communication circuit of the outdoor controller board
  3. Defective communication circuit of the indoor controller board
  4. Noise has entered the power supply or the indoor/outdoor connecting wire

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Connecting-wire and board work is a technician job.

Source

Mitsubishi Electric mini-split code E9: Indoor/outdoor unit communication error - transmitting error detected by the outdoor unit

Soft lockout

Indoor/outdoor unit communication error - transmitting error detected by the outdoor unit. The outdoor controller board could not find a free slot on the transmission path for 3 minutes.

Manual wording: “E9 Indoor/outdoor unit communication error - Transmitting error (Indoor unit)”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Indoor/outdoor unit connecting wire has contact failure or is miswired
  2. Defective communication circuit of the outdoor controller board
  3. Defective communication circuit of the indoor controller board
  4. Noise has entered the power supply or the indoor/outdoor connecting wire

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Connecting-wire and board work is a technician job.

Source

Mitsubishi Electric mini-split code EA: Miswiring of the indoor/outdoor unit connecting wire, or too many indoor units

Soft lockout

Miswiring of the indoor/outdoor unit connecting wire, or too many indoor units. The outdoor board could not automatically count the connected indoor units within 4 minutes of power-on, or it counted more indoor units than the outdoor unit supports.

Manual wording: “Miswiring of indoor/outdoor unit connecting wire - Outdoor controller circuit board can automatically check the number of connected indoor units. Abnormal if the number cannot be checked automatically due to miswiring.”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Contact failure or miswiring of the indoor/outdoor unit connecting wire
  2. Connecting wire diameter or length is outside the specified capacity (total wiring length limit 80 m)
  3. Too many indoor units connected to one outdoor unit (4 units or more)
  4. Defective transmitting/receiving circuit on the outdoor or indoor controller board
  5. Two or more outdoor units set to refrigerant address 0
  6. Noise on the power supply or connecting wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

This is almost always an installation wiring fault. The connecting wire order S1, S2, S3 and the unit count have to be checked by a technician.

Source

Mitsubishi Electric mini-split code EB: Miswiring of the indoor/outdoor unit connecting wire - converse

Soft lockout

Miswiring of the indoor/outdoor unit connecting wire - converse (reversed) wiring or disconnection. The outdoor board could not set the indoor unit number within 4 minutes of power-on.

Manual wording: “Miswiring of indoor/outdoor unit connecting wire (converse wiring or disconnection)”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Contact failure or miswiring of the indoor/outdoor unit connecting wire
  2. Connecting wire diameter or length is outside the specified capacity
  3. Defective transmitting/receiving circuit on the outdoor or indoor controller board
  4. Two or more outdoor units set to refrigerant address 0 in a group control system
  5. Noise on the power supply or connecting wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Reversed or disconnected connecting wires between indoor and outdoor units must be corrected by a technician.

Source

Mitsubishi Electric mini-split code EC: Startup time over

Soft lockout

Startup time over. The system could not finish its startup process within 4 minutes of power-on.

Manual wording: “Startup time over - The unit cannot finish startup process within 4 minutes after power on.”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Contact failure of the indoor/outdoor unit connecting wire
  2. Connecting wire diameter or length is outside the specified capacity
  3. Two or more outdoor units set to refrigerant address 0 in a group control system
  4. Noise on the power supply or connecting wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Connecting-wire condition and length are installation items only a technician should verify.

Source

Mitsubishi Electric mini-split code ED: Serial communication error inside the outdoor unit

Soft lockout

Serial communication error inside the outdoor unit. The outdoor controller board and the outdoor power board (or the M-NET board) cannot talk to each other.

Manual wording: “Serial communication error - Abnormal if serial communication between outdoor controller circuit board and outdoor power circuit board is defective.”

Documented for: PUZ-HA and other A-Control outdoor units with a separate power circuit board

Likely causes, most common first

  1. Breaking of wire or contact failure of connector CN2 between the outdoor controller board and the outdoor power circuit board
  2. Breaking of wire or contact failure of connector CN4 between the same two boards
  3. Defective communication circuit of the outdoor power circuit board
  4. Defective communication circuit of the outdoor controller circuit board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

This is entirely internal to the outdoor unit's control boards. Call a technician.

Source

Mitsubishi Electric mini-split code EE: Combination error between the indoor and outdoor units

Hard lockout

Combination error between the indoor and outdoor units. The indoor unit and outdoor unit that are wired together are not an approved pairing.

Manual wording: “EE - Combination error between indoor and outdoor units”

Documented for: A-Control indoor and outdoor units

Likely causes, most common first

  1. Indoor unit model and outdoor unit model are not a permitted combination
  2. Wrong indoor unit connected during a replacement

When to call a technician

The equipment pairing has to be corrected against Mitsubishi's compatibility table. Call a technician or the installer.

Sources

Mitsubishi Electric mini-split code EF: Non-defined check code

Warning

Non-defined check code. The controller received a check code it does not recognize.

Manual wording: “Non defined check code - This code is displayed when non-defined check code is received.”

Documented for: A-Control indoor and outdoor units

Likely causes, most common first

  1. Noise has entered the remote controller transmission wire
  2. Noise has entered the indoor/outdoor unit connecting wire
  3. Outdoor unit is not an inverter model

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

If EF repeats, the manual calls for replacing the indoor or outdoor controller board, or confirming the outdoor unit is a compatible inverter model. Call a technician.

Source

Mitsubishi Electric mini-split code FB: Indoor unit control system error

Hard lockout

Indoor unit control system error. Data cannot be read normally from the nonvolatile memory of the indoor controller board.

Manual wording: “Indoor controller board - Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board.”

Documented for: A-Control indoor units

Likely causes, most common first

  1. Defective indoor controller board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The manual's only remedy is to replace the indoor controller board. Call a technician.

Sources

Mitsubishi Electric mini-split code F3: The 63L low pressure switch connector

Soft lockout

The 63L low pressure switch connector (red) on the outdoor controller board is open. Detected when power is turned on.

Manual wording: “F3 63L connector(red) is open.”

Documented for: PUZ-HA and other A-Control outdoor units fitted with a low pressure switch

Likely causes, most common first

  1. 63L connector disconnected or has contact failure on the outdoor controller board
  2. 63L low pressure switch itself has failed or is tripped
  3. Defective outdoor controller circuit board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

63L is a refrigerant pressure safety switch. Never jumper or bypass it - a technician must find out why it is open.

Source

Mitsubishi Electric mini-split code F5: The 63H high pressure switch connector

Soft lockout

The 63H high pressure switch connector (yellow) on the outdoor controller board has been open for 3 minutes continuously after power-on.

Manual wording: “63H connector open - Abnormal if 63H connector circuit is open for 3 minutes continuously after power supply. 63H: High pressure switch”

Documented for: PUZ-HA and other A-Control outdoor units fitted with a high pressure switch

Likely causes, most common first

  1. Disconnection or contact failure of the 63H connector on the outdoor controller circuit board
  2. Disconnection or contact failure at the 63H switch itself
  3. 63H is working (tripped) because of defective parts
  4. Defective outdoor controller circuit board

What you can safely check yourself

  • Check that the outdoor unit is clear of snow, ice, leaves and debris so it can reject heat
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

63H is the high pressure safety switch. Never jumper or bypass it. A technician must check its continuity and find out why it opened.

Source

Mitsubishi Electric mini-split code U1: Abnormal high pressure

Soft lockout

Abnormal high pressure. The 63H high pressure switch opened at 602 PSIG during compressor operation, so the system shut down. Something is stopping the system from rejecting heat.

Manual wording: “High pressure (High pressure switch 63H worked) - Abnormal if high pressure switch 63H worked during compressor operation. *4.15 MPa [602PSIG]”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Short cycle of the indoor unit - supply air recirculating back into the return
  2. Clogged filter on the indoor unit
  3. Decreased airflow from a dirty indoor fan or dirty indoor heat exchanger
  4. Locked or malfunctioning indoor fan motor
  5. Stop valve not fully open
  6. Clogged or broken pipe
  7. Locked or malfunctioning outdoor fan motor
  8. Short cycle of the outdoor unit or dirty outdoor heat exchanger
  9. Disconnection or contact failure of the 63H connector on the outdoor controller board

What you can safely check yourself

  • Remove and clean or replace the indoor air filters
  • Clear anything blocking the indoor unit inlet or outlet
  • Check the outdoor unit is clear of snow, ice, leaves, grass clippings and stacked items, with open space all around
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

If the filters and outdoor coil are clean and U1 comes back, the refrigerant circuit, a fan motor or a stop valve is at fault. Never jumper the 63H switch. Call a technician.

Source

Mitsubishi Electric mini-split code U2: Abnormal high discharge temperature or high compressor surface temperature, which usually means the system is short of refrigerant

Soft lockout

Abnormal high discharge temperature or high compressor surface temperature, which usually means the system is short of refrigerant. The discharge thermistor TH4 exceeded 230F for 5 minutes, or the compressor surface thermistor TH33 exceeded 257F.

Manual wording: “Abnormal high discharge temperature, shortage of refrigerant ... Abnormal if TH4 exceeds 230F [110C] or more continuously for 30 seconds”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Shortage of refrigerant
  2. Defective operation of the stop valve (not fully open)
  3. Defective action of the linear expansion valve
  4. Clogging with foreign objects in the refrigerant circuit
  5. Defective discharge or compressor-surface thermistor
  6. Defective outdoor controller board

What you can safely check yourself

  • Check the outdoor unit is clear of snow, ice and debris
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

This code points at a refrigerant charge or expansion valve problem. Refrigerant work requires EPA certification and gauges. Call a technician.

Source

Mitsubishi Electric mini-split code U3: Open or short circuit of the outdoor discharge temperature thermistor

Soft lockout

Open or short circuit of the outdoor discharge temperature thermistor (TH4) or compressor surface thermistor (TH33). Detected when the sensor reads 37F or less (open) or 422F or more (short) during compressor operation.

Manual wording: “Open/short circuit of outdoor unit temperature thermistor (TH4, TH33) - Abnormal if open (37F [3C] or less) or short (422F [217C] or more) is detected during compressor operation.”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Disconnection or contact failure of connectors TH4 or TH33 on the outdoor controller circuit board
  2. Defective thermistor
  3. Defective outdoor controller circuit board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Thermistor testing happens inside the outdoor unit at the control board. Call a technician.

Source

Mitsubishi Electric mini-split code U4: Open or short circuit of one of the outdoor unit thermistors

Soft lockout

Open or short circuit of one of the outdoor unit thermistors (TH3 liquid, TH32 suction, TH6 two-phase pipe, TH7 ambient, TH8 heatsink), detected during compressor operation.

Manual wording: “Open/short of outdoor unit thermistors (TH3, TH32, TH6, TH7, and TH8) - Abnormal if open or short is detected during compressor operation.”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Disconnection or contact failure of the thermistor connectors on the outdoor controller circuit board or connector CN6 on the outdoor power circuit board
  2. Defective thermistor
  3. Defective outdoor controller circuit board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Identifying which of the five outdoor sensors failed requires the service tool and resistance measurements inside the outdoor unit. Call a technician.

Source

Mitsubishi Electric mini-split code U5: Abnormal temperature of the heatsink

Soft lockout

Abnormal temperature of the heatsink. The heatsink thermistor TH8 read 170F (HA24) or 177F (HA30/36/42) or higher, meaning the inverter electronics are overheating.

Manual wording: “Temperature of heatsink - Abnormal if heat sink thermistor(TH8) detects temperature indicated below. HA24: 170F [77C], HA30/36/42: 177F [81C]”

Documented for: PUZ-HA and other A-Control outdoor units

Likely causes, most common first

  1. The outdoor fan motor is not running
  2. Failure of the outdoor fan
  3. Airflow path is clogged
  4. Rise of ambient temperature around the outdoor unit
  5. Defective thermistor
  6. Defective input circuit on the outdoor power circuit board

What you can safely check yourself

  • Check that the outdoor unit has clear air space around it and is not blocked by fencing, plants, stored items, snow or leaves
  • Check that the outdoor fan is spinning when the unit runs
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

If the outdoor unit is clear and U5 returns, the fan motor, thermistor or power board is at fault. Call a technician.

Source

Mitsubishi Electric mini-split code U6: Power module abnormality / compressor overcurrent interruption

Soft lockout

Power module abnormality / compressor overcurrent interruption. The board checked the power module after detecting overcurrent (a UF or UP condition) and found it abnormal.

Manual wording: “Power module - Check abnormality by driving power module in case overcurrent is detected. (UF or UP error condition)”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Outdoor stop valve is closed
  2. Decrease of power supply voltage
  3. Looseness, disconnection or reversed connection of the compressor wiring
  4. Defective compressor
  5. Defective outdoor power circuit board

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Stop valves, compressor wiring and the inverter power module are all high-voltage refrigerant-circuit items. Call a technician.

Source

Mitsubishi Electric mini-split code U7: Too low superheat due to low discharge temperature

Soft lockout

Too low superheat due to low discharge temperature. Discharge superheat stayed at 5F or below for 3 minutes even with the linear expansion valve at its minimum opening, meaning liquid refrigerant is likely reaching the compressor.

Manual wording: “Too low superheat due to low discharge temperature - Abnormal if discharge superheat is continuously detected less than or equal to 5F [-15C] for 3 minutes”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Disconnection or loose connection of the discharge temperature thermistor (TH4)
  2. Defective high pressure or temperature sensing
  3. Disconnection or loose connection of the linear expansion valve or its connector
  4. Defective linear expansion valve
  5. Overcharge of refrigerant

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Expansion valve and refrigerant charge problems require gauges and EPA certification. Call a technician.

Source

Mitsubishi Electric mini-split code U8: Outdoor fan motor protection stop

Soft lockout

Outdoor fan motor protection stop. The board is not seeing the expected rotational speed from the DC outdoor fan motor - 100 rpm or below for 15 seconds at 68F or warmer outdoor air, or 50 rpm or below (or 1500 rpm or more) continuously for 1 minute.

Manual wording: “Outdoor fan motor - Abnormal if rotational frequency of the fan motor is not detected during DC fan motor operation.”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Failure in the outdoor DC fan motor
  2. Failure in the outdoor controller board

What you can safely check yourself

  • Turn the power off at the breaker first, then look for leaves, ice, a stick or other debris jamming the outdoor fan blade
  • Clear snow and ice from around and on top of the outdoor unit
  • Turn the system back on at the breaker once

When to call a technician

If nothing is physically jamming the fan and U8 returns, the fan motor or the control board has failed. Never reach into the outdoor unit with power on. Call a technician.

Source

Mitsubishi Electric mini-split code U9: Power supply abnormality - overvoltage, undervoltage, overcurrent or a bad power synchronous signal

Soft lockout

Power supply abnormality - overvoltage, undervoltage, overcurrent or a bad power synchronous signal. The PFC circuit saw DC bus voltage rise to 430 V, drop to 200 V, or input current fall out of range.

Manual wording: “PFC error (Overvoltage/Undervoltage/Overcurrent) - PFC detected any of the following: a) Increase of DC bus voltage as follows: 430 V”

Documented for: PUZ-HA and other A-Control outdoor units

Likely causes, most common first

  1. Abnormal increase in power source voltage
  2. Decrease in power source voltage or an instantaneous drop
  3. Disconnection or loose connection of the compressor wiring
  4. Misconnection of the reactor (DCL)
  5. Defective outdoor power circuit board
  6. Defective reactor (DCL)
  7. Disconnection or loose connection of CN2 between the outdoor power board and the controller board

What you can safely check yourself

  • Check whether the house has had a power flicker, brownout or storm outage recently
  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Measuring supply voltage at the unit and testing the reactor and power board are technician tasks. If the whole house has voltage problems, that is an electrician's call.

Source

Mitsubishi Electric mini-split code UD: Overheat protection

Soft lockout

Overheat protection. The outdoor pipe thermistor TH3 or the condensing temperature from the high pressure sensor read 158F or more during compressor operation, so the unit stopped to protect itself.

Manual wording: “Overheat protection - Abnormal if outdoor pipe thermistor (TH3), condensing temperature T63HS detects 158F [70C] or more during compressor operation.”

Documented for: PUZ-HA and other A-Control outdoor units

Likely causes, most common first

  1. Defective outdoor fan (fan motor), or short cycle of the outdoor unit during cooling operation
  2. Defective outdoor pipe thermistor (TH3) or condensing temperature sensor
  3. Defective outdoor controller board

What you can safely check yourself

  • Check that the outdoor unit is clear of snow, ice, leaves and stored items and has open air space around it
  • Check that the outdoor fan is spinning when the unit runs
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

If the outdoor unit is clear and Ud returns, the fan motor or a sensor has failed. Call a technician.

Source

Mitsubishi Electric mini-split code UE: Abnormal pressure at the 63HS high pressure sensor

Soft lockout

Abnormal pressure at the 63HS high pressure sensor. The sensor read 14.5 PSIG or less, which normally means the sensor or its connector has failed rather than that the system is actually empty.

Manual wording: “Abnormal pressure of 63HS - Abnormal if 63HS detects 14.5 PSIG [0.1 MPa] or less. 63HS: High pressure sensor”

Documented for: PUZ-HA and other A-Control outdoor units with a high pressure sensor

Likely causes, most common first

  1. Disconnection or contact failure of connector 63HS on the outdoor controller board
  2. Defective pressure sensor
  3. Defective outdoor controller circuit board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The pressure sensor is a refrigerant-circuit component inside the outdoor unit. Call a technician.

Source

Mitsubishi Electric mini-split code UF: Compressor overcurrent interruption with the compressor locked

Soft lockout

Compressor overcurrent interruption with the compressor locked. Overcurrent on the DC bus or compressor was detected within 30 seconds of the compressor starting, which points at a seized or stalled compressor.

Manual wording: “Compressor overcurrent interruption (When compressor locked) - Abnormal if overcurrent of DC bus or compressor is detected within 30 seconds after compressor starts operating.”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Stop valve is closed
  2. Decrease of power supply voltage
  3. Looseness, disconnection or reversed connection of the compressor wiring
  4. Defective compressor
  5. Defective outdoor power circuit board
  6. DIP switch setting difference on the outdoor controller circuit board

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

A locked compressor, closed stop valve or compressor wiring fault all require a technician. Do not keep resetting the breaker to force it to start.

Source

Mitsubishi Electric mini-split code UH: Current sensor error

Soft lockout

Current sensor error. Input current hit 38 A, or stayed at 34 A or more for 10 seconds (HA24-36 models; 44 A / 40 A on HA42).

Manual wording: “Current sensor error - It is abnormal for 38 A the input current or 10 seconds continuous 34 A or more. (HA24-36)”

Documented for: PUZ-HA and other A-Control outdoor units

Likely causes, most common first

  1. Defective current sensor circuit on the outdoor power circuit board
  2. Decrease of power supply voltage

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The current sensor lives on the outdoor power circuit board. Call a technician.

Source

Mitsubishi Electric mini-split code UL: Abnormal low pressure

Soft lockout

Abnormal low pressure. Three minutes after the compressor started, the temperature difference TH32 minus TH4 was 68F or more and TH32 exceeded 176F, which the control reads as a low pressure condition.

Manual wording: “Abnormal low pressure - Abnormal if TH32-TH4 is 68F [20C] or higher and TH32 exceeds 176F [80C] after compressor starts operating for 3 minutes.”

Documented for: PUZ-HA and other A-Control outdoor units

Likely causes, most common first

  1. Stop valve of the outdoor unit is closed during operation
  2. Leakage or shortage of refrigerant
  3. Malfunction of the linear expansion valve

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The manual's remedies are to check the stop valve, correct the refrigerant charge and check the expansion valve. All of that is a technician job.

Source

Mitsubishi Electric mini-split code UP: Compressor overcurrent interruption

Soft lockout

Compressor overcurrent interruption. Overcurrent on the DC bus or compressor was detected after the compressor had been running for 30 seconds or more.

Manual wording: “Compressor overcurrent interruption - Abnormal if overcurrent DC bus or compressor is detected after compressor starts operating for 30 seconds.”

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Stop valve is closed
  2. Decrease of power supply voltage
  3. Looseness, disconnection or reversed connection of the compressor wiring
  4. Defective fan on the indoor or outdoor units
  5. Short cycle on the indoor or outdoor units
  6. Defective indoor or outdoor coil
  7. Defective compressor
  8. Defective outdoor power circuit board
  9. DIP switch setting difference on the outdoor controller board

What you can safely check yourself

  • Remove and clean or replace the indoor air filters
  • Check that the outdoor unit is clear of snow, ice, leaves and stored items
  • Clear anything blocking the indoor unit inlet or outlet
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

If airflow is clear and UP returns, the compressor, its wiring, the stop valve or the power supply is at fault. Call a technician.

Source

How old is this Mitsubishi Electric?

Age changes what a fault code means for you. The same failure is a routine repair on a six-year-old unit and the end of the line on a twenty-year-old one. Your Mitsubishi Electric serial number has the build date in it.

Decode your Mitsubishi Electricserial number →

Manuals used for this page