York Furnace: 7 Flashes
A York furnace LED pattern starting with 7 flashes matches 2 documented codes: 7 red flashes, 7 red flashes (YP9C modulating). Watch the full pattern (short vs. long flashes) to tell them apart — all 2 are explained below.
Code 7 red flashes: The burners failed to light on three trials for ignition, so the control locks out for one hour and then tries again
The burners failed to light on three trials for ignition, so the control locks out for one hour and then tries again.
Manual wording: “7 RED FLASHES: This fault code indicates that the flame could not be established during three trials for ignition... The furnace will lock out for one hour and then restart.”
Documented for: TG8S, TG9S, TM9E, TM9X, TM8X, TM9T, TM8T, TM9V, TM8Y, TM9Y
Likely causes, most common first
- Gas valve switch left in the OFF position
- Low or no gas pressure
- Faulty gas valve
- Dirty or faulty flame sensor
- Faulty hot surface ignitor
- Loose wires or a burner problem
What you can safely check yourself
- Check that other gas appliances in the house (stove, water heater) still work - if none do, the gas supply is out
- Replace a dirty air filter
- Check the outside vent and intake pipes for blockage
- Cycle the furnace off and on once at the service switch to let it retry
When to call a technician
Anything past confirming you have gas to the house - ignitor, flame sensor, gas valve - is technician work in a live gas compartment.
A York furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation Manual - Single Stage PSC Residential Gas Furnaces, TG9S and GG9S Series (95.5% AFUE Multi-position), 1083287-UIM-A-0114 (Johnson Controls Unitary Products (York), TG9S*MP, GG9S*MP single-stage PSC 95.5% AFUE gas furnaces) · checked 2026-08-25
- Installation Manual - Single Stage PSC Residential Gas Furnaces, TG8S*MP / TGLS*MP / GG8S*MP / GGLS*MP (80% AFUE Multi-position / Standard Low NOx), 998491-UIM-B-1013 (Johnson Controls Unitary Products (York), TG8S*MP, TGLS*MP, GG8S*MP, GGLS*MP 80% AFUE single-stage gas furnaces) · checked 2026-08-25
- Installation Manual - Single Stage ECM Residential Gas Furnaces, TM9E Series (95% AFUE Multi-position), 1083163-UIM-A-0214 (Johnson Controls Unitary Products (York), TM9E*MP single-stage ECM 95% AFUE gas furnaces) · checked 2026-08-25
- Installation Manual - Two Stage Variable Speed ECM Residential Gas Furnaces, TM9V Series (96% AFUE Multi-position), 1083294-UIM-A-0114 (Johnson Controls Unitary Products (York), TM9V*MP two-stage variable-speed ECM 96% AFUE gas furnaces) · checked 2026-08-25
Code 7 red flashes (YP9C modulating): Lockout due to no ignition
Lockout due to no ignition. The control tried three times to light the burners and failed, so it locks out for one hour and then tries again.
Manual wording: “Seven Red Flashes - Lockout due to no ignition. The control will try three times for ignition. If flame cannot be established in three tries, the control will lockout for one hour and then will try again to light.”
Documented for: YP9C, YPLC modulating furnaces
Likely causes, most common first
- No or low gas supply
- Failed hot surface ignitor
- Faulty gas valve
- Dirty or faulty flame sensor
What you can safely check yourself
- Check that other gas appliances in the house still work
- Replace a dirty air filter
- Check the outside vent and intake pipes for blockage
- Cycle the furnace off and on once at the service switch to let it retry
When to call a technician
Ignitor, flame sensor and gas valve work all happen inside the live gas compartment. Call a technician.
A York furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation Manual - Modulating ECM Residential Gas Furnace with ECM Motor, Models YP9C*C / TP9C*C / CP9C*C / LP9C*C (Up to 98% Modulating Multi-position), 1083292-UIM-A-0114 (Johnson Controls Unitary Products (York), YP9C*C (York Affinity modulating), and the identical TP9C / CP9C / LP9C chassis) · checked 2026-08-25