HVAC Code Lookup

Rheem Furnace Code 44

Safety fault

Low pressure switch closed with the inducer off. The low pressure switch is proving closed before the inducer even starts, which it should never do. The control tests for this before every heat cycle. The manual warns the switch may be welded closed or deliberately bypassed in the field.

Manual wording: “LOW PRESSURE SWITCH CLOSED, INDUCER OFF ... The low pressure control (or switch) should not be closed when the inducer is not running. If it is, this is a sign of a serious condition. The switch may be welded closed or purposely bypassed in the field.

Documented for: (-)97V, (-)96V

Likely causes, most common first

  1. Faulty switch
  2. Pressure switch physically bypassed in the field
  3. Loose or faulty wiring
  4. Abnormally high negative pressure present on vent system without inducer running

When to call a technician

Technician only. This is a combustion-safety interlock that is not doing its job - it must be replaced or the field bypass removed, never left in place.

A Rheem furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.