HVAC Code Lookup

Daikin Mini-Split Code UH

Soft lockout

System abnormality, refrigerant system address undefined. The outdoor unit found an indoor unit that never got an auto-assigned address.

Manual wording: “UH System abnormality, refrigerant system address undefined

Documented for: RMXS and other multi-zone systems

Likely causes, most common first

  1. Improper connection of transmission wiring between indoor and outdoor unit
  2. Defective indoor unit PCB
  3. Defective main PCB (A1P)

What you can safely check yourself

  • If the system was just powered up for the first time, allow at least 12 minutes for auto-addressing before reading the code again

When to call a technician

If UH is still there after auto-addressing has had time to finish, a technician has to trace the transmission wiring between the indoor units and the outdoor unit.

A Daikin mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source