HVAC Code Lookup

Daikin Mini-Split Code UF

Soft lockout

System is not set yet. During the check operation, the number of indoor units communicating did not match the number that actually changed temperature - meaning the refrigerant piping and the wiring do not run to the same zones.

Manual wording: “UF System is not set yet

Documented for: RMXS and other multi-zone systems

Likely causes, most common first

  1. Stop valve is left closed
  2. Improper connection of transmission wiring between indoor unit and outdoor unit
  3. Failure to execute check operation
  4. Defective indoor unit PCB

When to call a technician

UF means the installation is crossed or incomplete - piping to one zone with wiring to another, or stop valves still closed. This has to go back to the installer.

A Daikin mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.