Daikin Mini-Split Code J7

Warning

Outdoor liquid pipe thermistor (R7T) abnormality. A short or open circuit was detected in the outdoor liquid line temperature sensor.

Manual wording: “J7 Outdoor liquid pipe thermistor (R7T) abnormality

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Disconnection of thermistor
  2. Defective outdoor liquid pipe thermistor (R7T)
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The sensor plugs into X13A on the outdoor main PCB - reconnecting or replacing it is technician work.

A Daikin mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.