Daikin Mini-Split Code J6
Warning
Outdoor heat exchanger thermistor or related abnormality. The outdoor coil temperature sensor is reading open or shorted.
Manual wording: “J6 Outdoor heat exchanger thermistor or related abnormality”
Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor
Likely causes, most common first
- Disconnection of the connector for the thermistor
- Defective outdoor heat exchanger thermistor
- Defective outdoor unit PCB
What you can safely check yourself
- Turn the system off at the breaker or disconnect switch and back on once
When to call a technician
The outdoor coil sensor drives defrost and high-pressure protection. A technician needs to check and replace it.
A Daikin mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.