Daikin Mini-Split Code E3

Soft lockout

Actuation of high pressure switch. The high-pressure safety switch opened because refrigerant discharge pressure climbed past its setpoint (about 4.15 MPa on Atmosphera, 4.0 MPa on RMXS).

Manual wording: “E3 Actuation of high pressure switch

Documented for: FTXM-W/V (Atmosphera), RMXS multi-split outdoor units

Likely causes, most common first

  1. Actuation of the high pressure switch (S1PH)
  2. Closed stop valve
  3. Disconnection of connector S40 or of the two terminals at the high pressure switch
  4. Broken S1PH harness
  5. Defective high pressure switch
  6. Defective outdoor unit PCB
  7. Defective high pressure sensor (multi-split)
  8. Instantaneous power failure (multi-split)

What you can safely check yourself

  • Check the outdoor unit is not blocked by leaves, snow, plants or a fence and has open space around it
  • Check the outdoor coil is not visibly plugged with dirt or cottonwood
  • Turn the system off at the breaker or disconnect switch and back on once after clearing anything blocking airflow

When to call a technician

Stop valve position, pressure switch testing and refrigerant charge are all technician work. Never bypass or jumper the high-pressure switch.

A Daikin mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.