Bryant Furnace: 3 Flashes
A Bryant furnace LED pattern starting with 3 flashes matches 11 documented codes: 31.2, 31.3, 31.6, 31.7, 32.1, 32.2, 33.1, 33.2, 34.1, 34.2, 34.3. Watch the full pattern (short vs. long flashes) to tell them apart — all 11 are explained below.
Code 31.2: Open secondary pressure switch
Open secondary pressure switch (HPS) - the high-heat pressure switch did not close, or reopened, when the control needed it.
Manual wording: “31 2 Open secondary pressure switch (HPS)”
Documented for: 912SE
Likely causes, most common first
- Restricted vent or blocked intake/exhaust termination
- Plugged condensate drain
- Excessive wind at the vent
- Disconnected or obstructed pressure tubing
- Defective inducer motor or low inducer voltage
- Defective pressure switch
What you can safely check yourself
- Go outside and check the furnace intake and exhaust pipes for snow, ice, leaves, or a nest and clear any blockage
- Check the condensate drain line and trap for a clog
- Replace a dirty air filter
When to call a technician
If the vents are clear and the drain is open, the inducer, pressure switch, or tubing needs a technician. Never jumper a pressure switch.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 31.3: Secondary pressure switch lockout - the secondary
Secondary pressure switch lockout - the secondary (high-heat) pressure switch failed to close after three trials.
Manual wording: “31 3 Secondary PS Lockout - failed to close secondary PS after three trials”
Documented for: 912SE
Likely causes, most common first
- Restricted or improperly sized vent
- Plugged condensate drain
- Obstructed or disconnected pressure tubing
- Failed inducer motor or pressure switch
What you can safely check yourself
- Check outdoor vent terminations for snow, ice or debris
- Check the condensate drain and trap for a clog
When to call a technician
Three failed attempts to make the pressure switch means the venting or the inducer needs a technician's inspection.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 31.6: Open secondary pressure switch - the high-heat pressure switch did not close for one minute after the gas valve closed, or it has reopened
Open secondary pressure switch - the high-heat pressure switch did not close for one minute after the gas valve closed, or it has reopened.
Manual wording: “31.6 OPEN SECONDARY PRESSURE SWITCH - HPS did not close for one minute after gas valve closed or has reopened.”
Documented for: 926TC
Likely causes, most common first
- Failed to close secondary pressure switch after three trials
- Excessive wind
- Restricted vent
- Defective inducer motor
- Low inlet gas pressure (if LGPS used)
- Inadequate combustion air supply
- Improper vent sizing
- Disconnected or obstructed pressure tubing
- Condensate drainage restricted or blocked
What you can safely check yourself
- Check the outdoor intake and exhaust pipes for blockage from snow, ice, leaves, or nests
- Check the condensate drain line and trap for a clog
When to call a technician
Vent sizing, inducer performance, and pressure switch calibration are technician diagnostics.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
Code 31.7: High heat only for the next cycle - the high-heat pressure switch failed to close within 75 seconds while transitioning from low to high heat
High heat only for the next cycle - the high-heat pressure switch failed to close within 75 seconds while transitioning from low to high heat.
Manual wording: “31.7 HIGH HEAT ONLY for next cycle- HPS failed to close in 75s when transitioning from low to high heat.”
Documented for: 926TC
Likely causes, most common first
- Same venting and pressure switch causes as code 31.6
What you can safely check yourself
- Check outdoor vent terminations for blockage
- Check the condensate drain for a clog
When to call a technician
If the furnace keeps forcing itself to high heat, have a technician check the high-heat pressure switch and venting.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
Code 32.1: Open main pressure switch
Open main pressure switch (LPS) - the main low-heat pressure switch is open when it should be closed.
Manual wording: “32 1 Open Main pressure switch (LPS)”
Documented for: 912SE
Likely causes, most common first
- Restricted vent or blocked intake/exhaust termination
- Plugged condensate drain
- Disconnected or obstructed pressure tubing
- Defective inducer motor
- Defective pressure switch
- Excessive wind
What you can safely check yourself
- Check outdoor intake and exhaust pipes for snow, ice, leaves, or a nest
- Check the condensate drain line and trap for a clog
- Replace a dirty filter
When to call a technician
If venting and drain are clear, the inducer or pressure switch needs testing by a technician.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 32.2: Open main pressure switch
Open main pressure switch. If the low-heat pressure switch stays open longer than 5 minutes or reopens, the inducer shuts off for 15 minutes before retrying. On a two-stage furnace this can force the next cycle to high heat only.
Manual wording: “32.2 OPEN MAIN PRESSURE SWITCH - If LPS is open longer than 5 minutes or has reopened, inducer shuts off for 15 minutes before retry.”
Documented for: 926TC
Likely causes, most common first
- Restricted or improperly sized vent
- Plugged condensate drain
- Obstructed pressure tubing
- Defective inducer motor or pressure switch
- Excessive wind
What you can safely check yourself
- Check outdoor vent terminations for snow, ice, or debris
- Check the condensate drain and trap for a clog
- Replace a dirty air filter
When to call a technician
Have a technician confirm vent sizing and pressure switch operation. Do not bypass the switch.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
Code 33.1: A switch has opened in the main limit circuit - the limit or flame rollout switch is open
A switch has opened in the main limit circuit - the limit or flame rollout switch is open. The blower runs 4 minutes or until the switch remakes. If the switch stays open longer than 3 minutes the code becomes lockout 13.
Manual wording: “33.1 A SWITCH HAS OPENED IN THE MAIN LIMIT - Indicates the limit or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer.”
Documented for: 926TC, 912SE
Likely causes, most common first
- Dirty filter or restricted duct system
- Loose blower wheel
- Defective switch or connections
- Defective blower motor
- Improper gas input adjustment
What you can safely check yourself
- Check and replace the air filter - a clogged filter is by far the most common cause
- Make sure supply registers and return air grilles are open and unblocked
- Make sure the furnace door is fully seated
When to call a technician
If the code returns after a filter change, the limit or rollout switch is tripping for a reason a technician must find. The flame rollout switch requires manual reset and must never be reset without diagnosing why it tripped.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 33.2: Lockout to high heat only for the current cycle, following limit circuit trips
Lockout to high heat only for the current cycle, following limit circuit trips.
Manual wording: “33.2 LOCKOUT - High Heat Only for current cycle.”
Documented for: 926TC
Likely causes, most common first
- Dirty filter or restricted duct system
- Loose blower wheel
- Defective switch or connections
- Defective blower motor
- Improper gas input adjustment
What you can safely check yourself
- Replace the air filter
- Open any closed supply registers and clear blocked return grilles
When to call a technician
Repeated limit trips need a technician to check airflow, blower performance, and gas input rate.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
Code 34.1: Ignition fault during four consecutive ignition trials - the furnace tried to light four times without proving flame
Ignition fault during four consecutive ignition trials - the furnace tried to light four times without proving flame.
Manual wording: “34.1 IGNITION FAULT - during four consecutive ignition trials.”
Documented for: 926TC, 912SE
Likely causes, most common first
- Gas valve turned off or manual shut-off valve closed
- Green/yellow ground wire not connected to the furnace sheet metal
- Flame sensor grounded or dirty
- Defective hot surface igniter
- Low inlet gas pressure
What you can safely check yourself
- Check that other gas appliances still work, confirming gas service is on
- Make sure the furnace door is fully closed and latched
When to call a technician
Checking the igniter, flame sense current, and gas valve requires opening a live gas appliance. Call a technician instead of attempting it.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 34.2: After successful ignition
After successful ignition (flame proven), flame was lost before the heating blower on-delay finished.
Manual wording: “34.2 AFTER SUCESSFUL IGNITION flame loss before heating blower on delay”
Documented for: 926TC, 912SE
Likely causes, most common first
- Oxide buildup on the flame sensor
- Low inlet gas pressure
- Poor control ground continuity
- Inadequate flame carryover or rough ignition
What you can safely check yourself
- Confirm other gas appliances in the house are working normally
When to call a technician
Flame loss right after ignition is a combustion and flame-sensing problem for a technician; do not attempt to clean or reposition the flame sensor yourself.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 34.3: After successful ignition
After successful ignition (flame proven), flame was lost after the heating blower on-delay.
Manual wording: “34.3 AFTER SUCCESSFUL IGNITION flame loss after heating blower on delay”
Documented for: 926TC, 912SE
Likely causes, most common first
- Oxide buildup on the flame sensor
- Low inlet gas pressure
- Poor control ground continuity
- Airflow disturbing the flame
What you can safely check yourself
- Check that the air filter is clean and supply/return vents are open
When to call a technician
Losing flame once the blower comes on often points at gas pressure or flame sensing. Have a technician measure flame current and manifold pressure.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25