Bryant Furnace Code 31.6

WarningShown as: Major code 31 on the LED (3 short, 1 long); 31.6 on the display

Open secondary pressure switch - the high-heat pressure switch did not close for one minute after the gas valve closed, or it has reopened.

Manual wording: “31.6 OPEN SECONDARY PRESSURE SWITCH - HPS did not close for one minute after gas valve closed or has reopened.

Documented for: 926TC

Likely causes, most common first

  1. Failed to close secondary pressure switch after three trials
  2. Excessive wind
  3. Restricted vent
  4. Defective inducer motor
  5. Low inlet gas pressure (if LGPS used)
  6. Inadequate combustion air supply
  7. Improper vent sizing
  8. Disconnected or obstructed pressure tubing
  9. Condensate drainage restricted or blocked

What you can safely check yourself

  • Check the outdoor intake and exhaust pipes for blockage from snow, ice, leaves, or nests
  • Check the condensate drain line and trap for a clog

When to call a technician

Vent sizing, inducer performance, and pressure switch calibration are technician diagnostics.

A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.