Amana Furnace Code 2
Soft lockoutShown as: 2 flashes, then a pause, repeating
Pressure switch stuck closed. The control saw the vent pressure switch already closed before the draft inducer started, so it will not light the burners.
Manual wording: “Pressure Switch stuck Closed”
Documented for: Amana AMS8, AMH8, ADS8, ADH8, AMEH8, AMES80, ACES80, AMSS92, AMSS96, ACSS96 (single red diagnostic LED)
Likely causes, most common first
- Induced draft blower pressure switch contacts sticking
- Shorts in the pressure switch circuit
- Induced draft blower is not operating
What you can safely check yourself
- Turn the furnace off at its power switch for about 30 seconds and back on once to see if the code clears
When to call a technician
A stuck pressure switch is a safety-proving device. It must be tested and replaced by a technician - never jumpered or bypassed.
A Amana furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.