Mitsubishi Electric Mini-Split Code UH

Soft lockout

Current sensor error. Input current hit 38 A, or stayed at 34 A or more for 10 seconds (HA24-36 models; 44 A / 40 A on HA42).

Manual wording: “Current sensor error - It is abnormal for 38 A the input current or 10 seconds continuous 34 A or more. (HA24-36)

Documented for: PUZ-HA and other A-Control outdoor units

Likely causes, most common first

  1. Defective current sensor circuit on the outdoor power circuit board
  2. Decrease of power supply voltage

What you can safely check yourself

  • Check that the breaker feeding the outdoor unit is on and has not tripped
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The current sensor lives on the outdoor power circuit board. Call a technician.

A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.