Mitsubishi Electric Mini-Split Code U5
Soft lockout
Abnormal temperature of the heatsink. The heatsink thermistor TH8 read 170F (HA24) or 177F (HA30/36/42) or higher, meaning the inverter electronics are overheating.
Manual wording: “Temperature of heatsink - Abnormal if heat sink thermistor(TH8) detects temperature indicated below. HA24: 170F [77C], HA30/36/42: 177F [81C]”
Documented for: PUZ-HA and other A-Control outdoor units
Likely causes, most common first
- The outdoor fan motor is not running
- Failure of the outdoor fan
- Airflow path is clogged
- Rise of ambient temperature around the outdoor unit
- Defective thermistor
- Defective input circuit on the outdoor power circuit board
What you can safely check yourself
- Check that the outdoor unit has clear air space around it and is not blocked by fencing, plants, stored items, snow or leaves
- Check that the outdoor fan is spinning when the unit runs
- Turn the system off at the breaker, wait one minute, and turn it back on once
When to call a technician
If the outdoor unit is clear and U5 returns, the fan motor, thermistor or power board is at fault. Call a technician.
A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Service Manual No. OCH750 Revised Edition-E - PUZ-HA Outdoor Units (May 2024) (Mitsubishi Electric, PUZ-HA24NHA1, PUZ-HA30NKA, PUZ-HA36NKA, PUZ-HA42NKA1 heat-pump outdoor units) · checked 2026-08-25