Mitsubishi Electric Mini-Split Code U3

Soft lockout

Open or short circuit of the outdoor discharge temperature thermistor (TH4) or compressor surface thermistor (TH33). Detected when the sensor reads 37F or less (open) or 422F or more (short) during compressor operation.

Manual wording: “Open/short circuit of outdoor unit temperature thermistor (TH4, TH33) - Abnormal if open (37F [3C] or less) or short (422F [217C] or more) is detected during compressor operation.

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Disconnection or contact failure of connectors TH4 or TH33 on the outdoor controller circuit board
  2. Defective thermistor
  3. Defective outdoor controller circuit board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Thermistor testing happens inside the outdoor unit at the control board. Call a technician.

A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.