Mitsubishi Electric Mini-Split Code P5
Soft lockout
Drain overflow protection / drain pump error. The float switch stayed underwater for 1 minute 30 seconds with the drain pump running, so the compressor and indoor fan shut off to stop water overflowing.
Manual wording: “Drain overflow protection operation - Suspensive abnormality, if drain float switch is detected to be underwater for 1 minute and 30 seconds continuously with drain pump on.”
Documented for: A-Control indoor units with a condensate pump (PKA-A, PLA-A, PEAD-A, PCA-A)
Likely causes, most common first
- Malfunction of the drain pump
- Defective drainage - clogged drain pump or clogged drain pipe
- Defective drain float switch, or the float caught on a moving part
- Defective indoor controller board
What you can safely check yourself
- Check the condensate drain line outside for a clog, kink, ice or debris
- Check the air filters and clean them, since a dirty filter can make condensate ripple onto the float switch
- Turn the system off at the breaker, wait one minute, and turn it back on once
When to call a technician
Clearing the internal drain pan, drain pump or float switch means opening the indoor unit. Call a technician, and do not run the unit while it is spilling water.
A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Indoor Unit Service Manual No. OCH761 Revised Edition-A - PKA-A LA Series (May 2021) (Mitsubishi Electric, PKA-A12LA, PKA-A18LA, PKA-A12LA.TH, PKA-A18LA.TH wall-mounted indoor units) · checked 2026-08-25