Mitsubishi Electric Mini-Split Code F5

Soft lockout

The 63H high pressure switch connector (yellow) on the outdoor controller board has been open for 3 minutes continuously after power-on.

Manual wording: “63H connector open - Abnormal if 63H connector circuit is open for 3 minutes continuously after power supply. 63H: High pressure switch

Documented for: PUZ-HA and other A-Control outdoor units fitted with a high pressure switch

Likely causes, most common first

  1. Disconnection or contact failure of the 63H connector on the outdoor controller circuit board
  2. Disconnection or contact failure at the 63H switch itself
  3. 63H is working (tripped) because of defective parts
  4. Defective outdoor controller circuit board

What you can safely check yourself

  • Check that the outdoor unit is clear of snow, ice, leaves and debris so it can reject heat
  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

63H is the high pressure safety switch. Never jumper or bypass it. A technician must check its continuity and find out why it opened.

A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.