Mitsubishi Electric Mini-Split Code ED

Soft lockout

Serial communication error inside the outdoor unit. The outdoor controller board and the outdoor power board (or the M-NET board) cannot talk to each other.

Manual wording: “Serial communication error - Abnormal if serial communication between outdoor controller circuit board and outdoor power circuit board is defective.

Documented for: PUZ-HA and other A-Control outdoor units with a separate power circuit board

Likely causes, most common first

  1. Breaking of wire or contact failure of connector CN2 between the outdoor controller board and the outdoor power circuit board
  2. Breaking of wire or contact failure of connector CN4 between the same two boards
  3. Defective communication circuit of the outdoor power circuit board
  4. Defective communication circuit of the outdoor controller circuit board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

This is entirely internal to the outdoor unit's control boards. Call a technician.

A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.