Mitsubishi Electric Mini-Split Code E7

Soft lockout

Indoor/outdoor unit communication error (transmitting error). The indoor controller board transmitted a '0' but a '1' was read back 30 times in a row, so the indoor unit cannot reliably send to the outdoor unit.

Manual wording: “Indoor/outdoor unit communication error (Transmitting error) - Abnormal if 1 receiving is detected 30 times continuously though indoor controller board has transmitted 0.

Documented for: A-Control indoor and outdoor units (M-Series and P-Series)

Likely causes, most common first

  1. Defective transmitting/receiving circuit of the indoor controller board
  2. Noise has entered the power supply
  3. Noise has entered the outdoor control wire

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

The manual's remedy is to power cycle and, if it repeats, replace the indoor controller board. Call a technician.

A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.