LG Mini-Split Code CH53
Soft lockoutShown as: Outdoor LED01 (red) blinks 5 times, LED02 (green) blinks 3 times
Communication failure from the outdoor unit to the indoor unit(s). Same fault family as CH05, but reported from the outdoor side - the outdoor board is not hearing the indoor unit.
Manual wording: “Communication failure between outdoor unit and indoor unit(s)”
Documented for: All LG residential mini-splits, single-zone and multi-zone
Likely causes, most common first
- No power on the indoor unit
- Indoor/outdoor unit power connection error, or the communication line not installed
- Improper connection at the terminal block for the communication wire
- Improper wiring of the communication L-N wire between indoor and outdoor units
- Communication error caused by external electrical noise
- Indoor/outdoor communication circuit parts burned, or no power due to a burned indoor or outdoor PCB
What you can safely check yourself
- Check the breakers for BOTH the indoor and outdoor unit are on and not tripped
- Check the outdoor disconnect switch next to the condenser is switched on
- Turn the system off at the breaker for three minutes, then back on
When to call a technician
If power is on at both units and CH53 stays, the interconnecting wiring or a control board is at fault. That is technician work.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
- Room Air Conditioner SVC Manual (General) - Trouble Shooting Guide with Error Code (LG Electronics, All LG single-zone room air conditioner / mini-split chassis (SW, SB, SC, S4, S5, SH, SA, SJ, SK)) · checked 2026-08-25