Fujitsu Mini-Split: 4 Flashes

A Fujitsu mini-split LED pattern starting with 4 flashes matches 3 documented codes: 41, 42, 44. Watch the full pattern (short vs. long flashes) to tell them apart — all 3 are explained below.

Code 41: Indoor room thermistor error

Soft lockoutShown as: OPERATION lamp blinks 4 times, TIMER lamp blinks 1 time, ECONOMY lamp blinking continuously

Indoor room thermistor error. The room temperature sensor in the indoor unit has read an impossible temperature, meaning it is open or shorted.

Manual wording: “Indoor Room Thermistor Error - Room temperature thermistor detected an abnormal temperature.

Documented for: RGLX, RL2/RLS2/RLS3/RLB/RLXB wall mounted, RLF/RLF1 multi-zone

Likely causes, most common first

  1. Open or shorted room temperature thermistor
  2. Thermistor resistance out of specification
  3. Failed indoor controller PCB

What you can safely check yourself

  • Turn the power off at the breaker for about 5 minutes and back on to see whether the code clears

When to call a technician

The room thermistor is behind the indoor unit's front panel and has to be ohm-checked against Fujitsu's resistance table. Have a technician replace it.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for Fujitsu code 41

Code 42: Indoor heat exchanger

Soft lockoutShown as: OPERATION lamp blinks 4 times, TIMER lamp blinks 2 times, ECONOMY lamp blinking continuously

Indoor heat exchanger (pipe) thermistor error. The evaporator coil pipe sensor has read an abnormal temperature, meaning it is open or shorted.

Manual wording: “Indoor Heat Ex. (Pipe) Thermistor Error - Evaporator pipe thermistor detected an abnormal temperature.

Documented for: RGLX, RL2/RLS2/RLS3/RLB/RLXB wall mounted, RLF/RLF1 multi-zone

Likely causes, most common first

  1. Open or shorted indoor pipe thermistor
  2. Thermistor resistance out of specification
  3. Failed indoor controller PCB

What you can safely check yourself

  • Turn the power off at the breaker for about 5 minutes and back on to see whether the code clears

When to call a technician

The pipe thermistor clips onto the evaporator coil behind the indoor unit's casing. Replacing it is a technician's job.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for Fujitsu code 42

Code 44: Human sensor error

WarningShown as: OPERATION lamp blinks 4 times, TIMER lamp blinks 4 times, ECONOMY lamp blinking continuously

Human sensor error. The occupancy (human) sensor on the indoor unit is not responding correctly to the control board.

Manual wording: “Human Sensor error - Check if the connector connection and if cable is open

Documented for: RGLX indoor units fitted with the human/occupancy sensor option

Likely causes, most common first

  1. Loose or removed human sensor connector
  2. Erroneous connection at the sensor plug
  3. Open sensor cable
  4. Failed sensor, or failed main PCB

What you can safely check yourself

  • Turn the power off at the breaker for about 5 minutes and back on to see whether the code clears

When to call a technician

Diagnosing this requires continuity and 5 VDC checks at connector CN67 on the main board. That is technician work.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for Fujitsu code 44