Carrier Furnace Code 24
Hard lockoutShown as: 2 short flashes, 4 long flashes
The 3-amp secondary voltage fuse on the control board is blown, which means there is a short somewhere in the 24 V low-voltage wiring.
Manual wording: “24 SECONDARY VOLTAGE FUSE IS OPEN - Check for: - Short circuit in secondary voltage (24V) wiring including thermostat leads.”
Documented for: 58SC0A, 58MCB, 58MVP, 58UVB
Likely causes, most common first
- Short circuit in the 24 VAC secondary wiring, including the thermostat leads
When to call a technician
Replacing the fuse without finding the short just blows the new fuse. A technician needs to isolate the shorted thermostat or accessory wire.
A Carrier furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.