Carrier Furnace Code 14.2

Safety faultShown as: Major code 14 flashed on the LED (1 short, 4 long); 14.2 on the 3-digit display

Flame lost lockout. The flame signal was lost three times after the heating blower on-delay. The control auto-resets after 3 hours.

Manual wording: “14.2 FLAME LOST LOCKOUT - Flame signal was lost 3 times after heating blower on delay. Control will auto-reset after 3 hours. See status code 34.3.

Documented for: 58SC0B/58SC1B

Likely causes, most common first

  1. Incorrect manifold pressure or gas firing rate
  2. Gas inlet pressure fluctuations
  3. Flame sensing problem - see code 34

What you can safely check yourself

  • Check that the furnace filter is clean and vents are open, since airflow problems can disturb the flame

When to call a technician

Losing an established flame repeatedly is a combustion problem. Have a technician check manifold pressure, gas supply pressure, and the flame sensing circuit before running the furnace.

A Carrier furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.