Fujitsu Mini-Split Code A5

Soft lockoutShown as: OPERATION lamp blinks 10 times, TIMER lamp blinks 5 times, ECONOMY lamp blinking continuously

Low pressure error. Suction pressure stayed at or below 7.35 PSI for 5 minutes, repeating 5 times within 2 hours, so the system stopped.

Manual wording: “Low Pressure Error - Protection stop by suction pressure 7.35 PSI continued for 5 minutes, repeats 5 times within 2 hours.

Documented for: Single-zone (1-to-1) matched systems; RGLX, RLS3/RLB/RLXB, RLF/RLF1

Likely causes, most common first

  1. Closed or partly closed 3-way (gas side) service valve
  2. Clogged strainer
  3. Failed electronic expansion valve coil
  4. Low refrigerant charge or a refrigerant leak
  5. Failed suction pressure sensor

What you can safely check yourself

  • Note the outdoor temperature when the code appeared - Fujitsu says this code only shows up when outdoor ambient drops below 32 F
  • Turn the power off at the disconnect for about 5 minutes, then restore power

When to call a technician

Fujitsu classes A5 as a fix-on-fail code that must be serviced on site by a licensed technician, with running pressures checked on gauges and a leak check performed. It also requires function setting F3-40 to fully reset.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.