Fujitsu Mini-Split Code A1
Soft lockoutShown as: OPERATION lamp blinks 10 times, TIMER lamp blinks 1 time, ECONOMY lamp blinking continuously
Discharge temperature error. The compressor discharge line reached 230 F (110 C) during operation twice within 24 hours, so the system stopped to protect the compressor.
Manual wording: “Discharge Temperature Error - Protection stop by discharge temperature 230F (110C) during compressor operation generated 2 times within 24 hours.”
Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series
Likely causes, most common first
- Closed or partly closed 3-way service valve
- Restricted electronic expansion valve or clogged strainer
- Outdoor fan or heat exchanger not rejecting heat (dirty coil, blocked airflow)
- Low refrigerant charge or a refrigerant leak
- Failed discharge thermistor
What you can safely check yourself
- Clear anything blocking airflow at the outdoor unit - leaves, snow, stored items, overgrown shrubs
- Check the outdoor coil for heavy dirt or cottonwood buildup
- Turn the power off at the disconnect for about 5 minutes, then restore power
When to call a technician
Fujitsu's checklist is service valves, expansion valve, strainer, and a leak check with gauges. All of that is licensed refrigeration work - do not open service valves yourself.
A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- 410A Mini-Split Troubleshooting Guide (Part # 6-26-FG2020 Rev. 5/2019) (Fujitsu General America, Inc., All R410A Halcyon mini-splits: RGLX, RL2/RLS3/RLS3H/RLS3Y/RLB/RLXB/RLXEH wall mounted, RLF/RLF1 multi-zone indoor units, RLXFZ multi-zone outdoor units, RML/RMLQ, RULX/RSLX universal-mount, RCLX cassettes) · checked 2026-08-25
- Discharge Temperature Error - Fujitsu General Help Center (Fujitsu General America, Inc., RL2, RLS3, RLS2, RLB/RLXB, RLF, RLF1, LUAS1, LMAS, LZBS, LZAS, LPAS, RGLX, RLE series) · checked 2026-08-25