Fujitsu Mini-Split Code 97
Soft lockoutShown as: OPERATION lamp blinks 9 times, TIMER lamp blinks 7 times, ECONOMY lamp blinking continuously
Outdoor unit fan motor error. The outdoor fan turned slower than 100 RPM within 20 seconds of starting; after three repeats inside 60 seconds the compressor and fan both stop.
Manual wording: “Outdoor Unit Fan Motor Error - When outdoor fan motor rotation speed is less than 100 RPMs in 20 seconds after fan motor starts, fan motor stops.”
Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series
Likely causes, most common first
- Outdoor fan blade obstructed, iced, or the motor is locked
- Excessive ambient temperature around the fan motor from nearby heat-producing equipment
- Outdoor fan motor windings out of specification, or missing DC supply to the motor
- Failed outdoor main PCB
What you can safely check yourself
- With the power off at the disconnect, look for leaves, ice, or debris jamming the outdoor fan blade
- Clear snow and ice buildup from around and on top of the outdoor unit
- Turn the power off at the disconnect for about 5 minutes, then restore power
When to call a technician
Fujitsu's next steps are ohming the fan motor windings and checking DC voltage to the motor. That means a licensed technician.
A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- 410A Mini-Split Troubleshooting Guide (Part # 6-26-FG2020 Rev. 5/2019) (Fujitsu General America, Inc., All R410A Halcyon mini-splits: RGLX, RL2/RLS3/RLS3H/RLS3Y/RLB/RLXB/RLXEH wall mounted, RLF/RLF1 multi-zone indoor units, RLXFZ multi-zone outdoor units, RML/RMLQ, RULX/RSLX universal-mount, RCLX cassettes) · checked 2026-08-25