WarningShown as: OPERATION lamp blinks 5 times, TIMER lamp blinks 7 times, ECONOMY lamp blinking continuously

Damper error. The limit switch did not confirm the upper airflow damper reached the closed position.

Manual wording: “Damper Error - When limit switch was not able to detect the closing though the damper is closed. (Upper air flow)

Documented for: RLF multi-zone indoor units with a motorized upper airflow damper

Likely causes, most common first

  1. Something obstructing the damper's travel
  2. Damper mechanism binding or damaged
  3. Loose connector CN18, or a shorted/pinched wire
  4. Failed limit switch

What you can safely check yourself

  • Look for an obvious obstruction in front of the indoor unit's air outlet louvers

When to call a technician

The damper limit switch and its harness are inside the indoor unit's casing. A technician must check them.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.