Fujitsu Mini-Split Code 26

Soft lockoutShown as: OPERATION lamp blinks 2 times, TIMER lamp blinks 6 times, ECONOMY lamp blinking continuously

Address setting error in the wired remote controller system. Auto-set and manually-set controller addresses are mixed in one remote controller group, or the same address number is duplicated in one group.

Manual wording: “Address Setting Error in Wired Remote Controller System - When the address number set by auto setting & manual setting are mixed in on RC group.

Documented for: RGLX, RL2/RLS3/RLB/RLXB, RLF/RLF1 with UTY-series wired remote controllers

Likely causes, most common first

  1. Wrong wiring connection within the remote controller group
  2. Auto address (00) and a manual address mixed in one remote controller group
  3. Duplicate remote controller addresses in one group
  4. Damaged indoor controller PCB

When to call a technician

Remote controller addressing is a commissioning setting done through the wall controller's service menus. Call the installing contractor.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.